Materials of Construction
DP 12.4 PSI @ 242.6 GPM |
In the aviation industry, a differential pressure of more than 25 PSID across the full flow fuel monitor is considered unacceptable according to ATA Specification 103. A differential pressure more than 15 PSID across a water coalescer is considered unacceptable. The differential pressure transducer has a maximum differential pressure of 60.0 PSID. Interlocks on the LCR-II and LCR 600 electronic registers, if employed, shut down fuel delivery if the differential pressure reaches or exceeds the programmed differential pressure shutdown value.
This system is designed for application on Jet Fuel delivery vehicles, hydrant carts, and stationary systems and is currently available for use with the Liquid Controls LectroCount® LCR-II® Electronic Register with SR214 operating software (version 4.04 or higher) and compatible ticket software or the LCR 600 Electronic Register with standard software.
Environmental Rating:
IP67 (similar to NEMA 4X)
Safety:
Designed to meet Class I, Division 2
Groups C and D requirements
Applicable Products:
Class 2: Jet Fuel
Communication Protocol:
RS485
Pressure Rating:
Differential measurement range
• 0-43.5 PSID (0 to 3 bar) for rated accuracy
[60 PSID (4 bar) overpressure limit]
Line pressure range:
• 0 to 150 PSI (0 to 10.3 bar)
Accuracy:
±0.2% of full scale
(±0.088 PSID from -4º to 104ºF, -20º to 40ºC)
Power:
+10 to 28VDC, <4mA
Temperature Limits:
-40° to 176°F (-40° to 80°C)
Electronics Installation Manuals